Whiddy Island Bantry Co. Cork - Ground-source heat pump

Heating & Cooling was always a problem with the control tower of Bantry Terminals – oil storage depot on Whiddy Island. 3 walls of glass – single glazed resulted in huge temperature swings in any 24 hour period . 

The loss of a complete computer server system due to over heating in the control tower cellar prompted the requirement of air conditioning. AHAC installed this unit.


Scope of Alternative Heating & Cooling Ltd (A.H.A.C)  Work  

1. Design of Ground Source Heat Pump (G.S.H.P) System installation

2. Supply, install and commission complete heat pump system

 

 

 

 

Building type:

Commercial Control Room

Location:

Bantry, Co. Cork

Year of construction:

1960’s

Type of construction

Brick

Total Floor area (m2)

72² - control tower only

Number of storeys:

2

Type of heat distribution system:

Forced air ventilation

% of total floor area heated:

100%

Design outdoor temperature (ºC)

Heating:

6

Cooling:

- N/A

Design indoor temperature (ºC)

Heating:

25

Cooling:

- N/A

 

 

Heating and cooling Loads

Application:

Space heating and cooling only

Heat pump type(s):

Water-to-air

Manufacturer

Waterfurnace

 

Cooling:

-

Model

Premier (PK08)

Heat pump installed capacity (KW)

Heating: 8Kw    Cooling 10Kw

Refrigerant:

R-22

Heat source

Ground

Details (circulating pumps):

245 W (ground-source) + 200W (Fan)

a) Type of ground heat exchanger:

Vertical Closed loop

b) Depth (m):

110 m

c) Pipe length (m):

240m

d) Heat transfer fluid:

Water/glycol 20%

 

 

Distribution system(s):

 

 

Cooling:

- Available

Supply and return temperature (ºC)

 

18/30 air

 

  24/15 air

 

 

 

 

 

Hot water capacity

N/A

Auxiliary system:

None

Heat pump design:

100% of heating

140% of Cooling

Supplementary system:

1.5 Kw electric panel heaters

Ventilation

Natural

Heat pump system completion date:

2003

Comments:
  • Cooling performance on this unit out performs that of the heating. By the nature of the duct design – Full air ventilation of both the basement and the control tower is effected. Savings on the heating is substantial. 12kw of electric panel heaters were removed.
  • This heat pump runs at 1.8kw total consumption – compressor & delivery therefore saving Bantry terminals a staggering 80% on the heating bill. The cost of cooling is out weighed by the breakdown prevention of a computer control system for the entire tankfarm complex.  
 

 

 