Nenagh Co. Tipperary - Ground-source heat pump  

Waterfurnace Heat Pumps were chosen to drive this WHI Underfloor heated house. With this size of house, running costs were high on the selection criteria. 

AHAC’s design of the integration into the distribution system has provided the client with a combination of flexibility and user friendly operation.

Building and design values 

Scope of Alternative Heating & Cooling Ltd (A.H.A.C)  Work  

1. Design of Ground Source Heat Pump (G.S.H.P) System installation

2. Supply, install and commission complete heat pump system

 

 

Building type:

2 Storey dwelling & adjoining garage

Location:

Nenagh, Co. Tipperary

Year of construction:

2001

Type of construction

Block Cavity Insulation

Total Floor area (m2)

470 m²

Number of storeys:

2

Type of heat distribution system:

Underfloor heating throughout

% of total floor area heated:

80%

Design outdoor temperature (ºC)

Heating:

-3

Cooling:

- N/A

Design indoor temperature (ºC)

Heating:

21

Cooling:

- N/A

 

 

Heating and cooling Loads

Application:

Main Block of house heated by underfloor heating upstairs and downstairs.

Heat pump type(s):

Water-to-water

Manufacturer

Waterfurnace

 

Cooling:

 

Model

EKW17 & EKW12

Heat pump installed capacity (KW)

Heating: 30Kw

Refrigerant:

R-410A

Heat source

Ground - Horizontal

Details (circulating pumps):

450 W (ground-source) + 245W (distribution per floor)

a) Type of ground heat exchanger:

Horizontal

b) Trench area:

800 m²

c) Pipe length (m):

1600m

d) Heat transfer fluid:

Water/glycol 20%

 

 

Distribution system(s):

Underfloor heating

35/25

Cooling:

- not used

Supply and return temperature (ºC)

Underfloor Heating:

30/25

 

 

 

 

 

 

 

Hot water capacity

500 L

Auxiliary system:

None

Heat pump design:

100% of building load as determined by the under floor heating contractor.

Supplementary system:

Open fireplaces

Ventilation

Wall vents

Heat pump system completion date:

2004

Comments:
Quality of insulation has shown its worth in this 5000 sq ft house.  
Good ground conditions coupled with a slightly modified underfloor heating system has delivered excellently.
 

 

 